Heat Recovery Continued...

Operation of the Heat Exchanger Element Operation of the Heat Exchanger Element
Control System BRC1D527Control System BRC1D527

Independent operation of HRV unit
Simultaneous ON/OFF of HRV and air conditioner
Filter sign display and reset
Timer settings, 7 day clock
Airflow rate switching (initial setting)
Ventilation mode switching (initial setting)
Self diagnostic functions
Quiet Operation

Sound pressure levels are remarkably low at 36 dB(A) for the VAM1000FA.

dB (A) Percieved Loudness Sound
0 Threshold of hearing -
20 Extremely soft Rustling leaves
40 Very soft Quiet room
60 Moderately loud Normal conversation
80 Very loud City traffic noise
100 Extremely loud Symphonic orchestra
120 Threshold of feeling Jet taking off

Specification for VAM1000FA at “High” fan speed (other sizes available):

Model VAM1000FA
Dimensions, mm (H x W x D) 348 x 988 x 1140
Duct connections (diameter) 250 mm
Air flow rate 278 litres/sec
Temperature exchange efficiency 75%
External static 98 Pa
Weight 61 kg
Sound pressure level 36 dB(A)
Electrical supply 240v/1ph/50hz
Running current 3.4 Amps
Fuse size 13 Amps
Operating range -15°C to 50°C db, 80% RH or less